Silicone Rubber Motor Lead - Type SRML
| 600V | 150°C-180°C-200°C *(See Below) |
|
UL AWM Style 3101, 3231 and 3278 OSHA Acceptable |
||||||||||
![]() |
DESCRIPTION: | ||||||||||||
|
|||||||||||||
| PART NO. | COND. SIZE (AWG) AND STRANDING |
INSUL. THICK. INCHES |
GLASS BRAID |
NOM. O.D. INCHES |
AMPS* | APPROX. WT/M' LBS |
UL STYLE |
| M4114+ | #10 (105/30) | .047 | .005 | .236 | 75 | 56 | 3101 |
| M4115 | #8 (133/29) | .062 | .010 | .302 | 100 | 92 | 3278 |
| M4116 | #6 (133/27) | .345 | 135 | 130 | |||
| M4117 | #4 (133/25) | .400 | 205 | 192 | 3231 | ||
| M4118 | #2 (133/23) | .467 | 240 | 282 | |||
| M4120 | #1/0 (259/24) | .078 | .015 | .610 | 385 | 468 | |
| M4121 | #2/0 (259/23) | .660 | 450 | 545 | |||
| M4122 | #3/0 (259/22) | .770 | 520 | 670 | |||
| M4123 | #4/0 (259/21) | .785 | 600 | 820 |
| * Based on single
conductor in free air 30°C ambient, 200°C conductor
temperature. Cable rated for intermittent use at 200°C
and continuous use at 180°C per IEEE specification
except #10, #8, and #6 AWG - Rated at 150°C. + Not UL Listed REV 8/97 |